Operating ambient temperatures
Suggested retail price
Technology
Multi-Bend Heat Exchanger
Increased heat. This unit uses the heat exchangers with tubes of a special design, the inner surface of which has trapezoidal notches "Innergrove cooper", which provides maximum heat transfer surface area increased. Due to this heat increases by 28%, reduced power consumption, and hence increases the efficiency of the system.
Sine-Wave Inverter
Technology 180° -gradusnogo wave inverter conversion - control voltage without the "pulse" effects (jagged sinusoid).
Compared with the current standard of 120° rectangular wave has the following advantages:
- Ability to work with a wider range of supply voltage and frequency.
- Most of the energy efficiency and energy conservation.
- More soft start, lower noise and vibration.
- more control.
Wi-Fi Control
Conditioners can optionally be equipped with a Wi-Fi module that allows the user to monitor and remotely control the air-conditioner from a smartphone or tablet from anywhere in the world.
Compresor DC inverter
Compressor with inverter DC can increase the efficiency of the air conditioner, thus reducing power consumption saves your costs. This system is much more economical and safer than air conditioners with a constant output of the compressor.
The heater of the outdoor unit pallet
Подогреватель поддона наружного блока устанавливается для обеспечения полного удаления воды образовавшейся в результате оттайки теплообменника наружного блока, после проведении режима "разморозки". Может изготавливаться из различных материалов.
Description
Heat pumps (HP) of the ISW series are available in split versions to meet the needs of the client.
Compared to standard heat pumps in this power range, which usually need to be integrated with a boiler or electric heaters, the ISW heat pump is designed to operate in monovalent mode, without the need for additional heaters or integrated heating elements.
In this way, it guarantees maximum energy savings and at the same time avoids the need to connect to a traditional heating network.
The ISW series HP model range will be supplied with a thermal output of 10,16,18,24, 28 kW (capacity is indicated at A7-W35 temperatures), the 10kW model is powered by 220V / 1F, the rest of the models are powered by 380V / 3F, all they are without electric heating elements in the indoor unit. Electricity consumption 2.2 - 3.6 - 4.1 - 6.5 - 8 kW, respectively (at rated load).
The outdoor units use specialized Panasonic EVI DC-inverter compressors running on R-410a freon, the outdoor unit fan motors are also equipped with DC motors, which made it possible to achieve energy efficiency in class A + according to the EU Technical Regulation for heating heat pumps.
Each outdoor unit comes with 4 m.p. copper pipe - flared at the ends, with nuts, in thermal insulation - for quick installation of the interblock route.
Specifications
FULL DC INVERTER HOT WATER + HEATING+COOLING EVI HEAT PUMP (SPLIT) | ||||||
IDEA PRO MODEL | Зовн / внутр блоки | ISW-10SF1-DN1 / ISW-10SF1-SPM | ISW-15SF1-DRN1 / ISW-15SF1-SPM | ISW-18SF1-DRN1 / ISW-18SF1-SPM | ISW-24SF1-DRN1 / ISW-24SF1-SPM | ISW-32SF1-DRN1 / ISW-32SF1-SPM |
Working Temperature Range | -25~43℃ | |||||
Power Supply | 220-240V/50Hz | 380-415V/50Hz | 380-415V/50Hz | |||
A7W35 | Heating capacity (min-max) (kW) | 10(3-11) | 15(4-16) | 18(4-20) | 24(5-27) | 32(5-35) |
Input power (kW) | 2.30 | 3.72 | 4.42 | 6.00 | 8.00 | |
Rated current (A) | 10.50 | 5.70 | 6.70 | 9.10 | 9.10 | |
COP | 3.75~4.6 | 3.82~4.58 | 376~4.62 | 3.9~4.6 | 3.74~4.58 | |
A2W45 | Heating capacity(min-max) (kW) | 7.8(3-8) | 12.5(5-13) | 15(4-16) | 19(5-20) | 25(5-27) |
Heating input power(kW) | 2.32 | 3.80 | 4.55 | 5.80 | 7.70 | |
Rated current (A) | 11.00 | 5.80 | 7.00 | 9.00 | 12.00 | |
COP | 3.36 | 3.30 | 3.30 | 3.28 | 3.25 | |
A35W7 | Cooling Capacity/EER (kW) | 7/2.81 | 11/2.8 | 14/2.8 | 19/2.7 | 25/2.75 |
Rated Cooling Input Power/Current(kW/A) | 2.5/11.3 | 3.95/6.1 | 5.0/8.0 | 7.0/10.0 | 9.1/14 | |
Heating Outlet hot water temperature range (℃) | 25-60 | |||||
Cooling Outlet water temperature range (℃) | 7-12 | |||||
IP Grade (Level of protection) | IPX4 | |||||
Anti-electric shock Rate | I | |||||
Noise (dB(A)) | ≤55 | ≤60 | ≤60 | ≤70 | ≤70 | |
Net weight/Gross weight(kg) | 105/115 | 160/175 | 190/205 | 220/215 | 250/215 | |
Diameter of pipe (mm) | DN25 | DN25 | DN32 | DN32 | DN32 | |
Cabinet material plate | Galvanized steel/Spray/Gray | |||||
Machine size | Outdoor unit (W*D*H) | 880*420*790 | 930*410*1270 | 1018*450*1366 | 1150*480*1440 | 1240*480*1630 |
Indoor unit (W*D*H) | 380*330*685 | 380*330*685 | 450*330*815 | 550*420*920 | 550*420*920 | |
Packing size(W*D*H) | Outdoor unit (W*D*H) | 980*520*970 | 1030*510*1450 | 1120*550*1480 | 1300/580/1600 | 1380/580/1730 |
Indoor unit (W*D*H) | 420*450*720 | 420*450*720 | 520*420*910 | 650*520*1010 | 650*520*1010 | |
Compressor | Panasonic Rotary EVI DC inverter / Mitsubishi Inverter | |||||
Refrigerant/Weight (Kg) | R410/2.2 | R410/ 2.6 | R410/ 2.8 | R410/ 3.6 | R410/ 4.6 | |
Fan Motor | DC VariableSpeed Motor | |||||
Condenser | SS 316 Brazed Plate Heat Exchanger | |||||
Water pump | Wilo | Wilo | Wilo | Grundfos | Grundfos | |
Expansion tank | 2L | 2L | 2L | 5L | 5L | |
Four-way valve | Sanhua | Sanhua | Sanhua | Sanhua | Sanhua | |
Controller | 7m Wired controller touch screen display + WIFI controller | |||||
Copper pipe Diameter High/Low (inch) | 3/8"+ 5/8" | 1/2" + 7/8" | ||||
Expansion valve | Sanhua | |||||
Water Road Electric Heater | Optional (2kW Extra) | Optional(2kW Extra) | ||||
Low-voltage switch | 0.15/0.05MPa | 0.15/0.05MPa | 0.15/0.05MPa | |||
High-voltage switch | 3.6/4.2MPa | 3.6/4.2MPa | 3.6/4.2MPa | |||
Package | Polywood packing | |||||
Weight | Outdoor unit (kg) | 68 | 95 | 105 | 155 | 185 |
Indoor unit (kg) | 32 | 37 | 40 | 75 | 80 | |
Remark: A7W35 working condition: Dry bulb temperature 7℃, Wet bulb temperature6℃. Outlet water temperature 35℃. A2W45working condition: Dry bulb temperature 2℃, Wet bulb temperature1℃. Outlet water temperature 45℃. A35W7 cooling conditions: Ambient temperature 35°C, inlet water temperature 12°C, outlet water temperature 7°C. |